Powerware 5115
|
|
Rating
|
500VA
|
750VA
|
1000VA
|
1400 VA
|
|
Part number
|
05146549-5501
|
05146555-5501
|
05146561-5501
|
05146567-5501
|
|
Capacity (VA/Watts)
|
500/320
|
750/500
|
1000/670
|
1400/950
|
|
Dimensions WxDxH (mm)
|
150x268x185
|
150x333x185
|
150x333x185
|
150x388x185
|
|
Weight (kg)
|
8
|
12
|
13
|
17
|
|
Input connection
|
IEC320/ 10A
|
IEC320/10A
|
IEC320/10A
|
IEC320/10A
|
|
Output connection
|
4xIEC320 10A
|
4xIEC320 10A
|
6xIEC320 10A
|
6xIEC320 10A
|
|
Typical runtime (Full load)
|
5 min
|
6 min
|
5 min
|
5 min
|
|
Operational
|
|
Nominal input voltage (Vac)
|
220/230/240 Vac
|
|
Input voltage range
|
184-276 VAC (+/-20% of nominal)
|
|
Operating frequency
|
50/60 Hz auto sensing
|
|
Input power factor
|
Same as load
|
|
Nominal output voltage
|
220/230/240 Vac
|
|
Output voltage regulation
|
-10%/+6% of selected nominal Voltage
|
|
Overload capacity
|
110% 3 min; 150% 10 cycles
|
|
Efficiency
|
95%
|
|
User interface
|
|
LED
|
Four LEDs; UPS on, UPS on battery, overload, alarm
|
|
Standard communication ports
|
RS232
|
|
Optional
|
External SNMP adapter
|
|
Environmental
|
|
Operating temperature
|
0ºC to +40 ºC
|
|
Storage temperature
|
-15ºC to +55 ºC
|
|
Altitude
|
< 3000 m
|
|
Audible noise at 1 meter
|
< 40dB
|
|
Certification
|
|
Markings
|
CE/GS/UL
|
|
Safety
|
EN 50091-1-1 & UL 1778
|
|
EMC
|
EN 50091-2, EN6100-3-2
|